579-1015 Rev U
4100ES Extended Power Supply Installation Instructions
*05791015U*
Cautions, warnings, and regulatory information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
Ground yourself before opening or installing components.
Prior to installation, keep components wrapped in anti-static material at all times.
Introduction
The Extended Power Supply (EPS) is a fire alarm control unit (FACU) power supply that supports the enhanced feature set of Simplex addressable
notification appliances.
With three Signaling Line Circuits (SLC), the EPS provides continuous power and control to three separate channels of addressable notification
appliances.
There are two available configurations for the EPS*:
EPS: This is the basic EPS configuration.
4100-5325 - 120 V 50 Hz/60 Hz EPS
4100-5327 - 220 V/230 V/240V 50 Hz/60 Hz EPS
EPS with IDNet: This refers to an EPS board fitted with an IDNet2 or IDNet1+ card.
4100-5311 - 120 V 50 Hz/60 Hz EPS
4100-5313 - 220 V/230 V/240V 50 Hz/60 Hz EPS
For use with revision 1.04 or higher of the ES Panel Programmer Software.
Important: Verify FACU system programmer, executive, and slave software compatibility when installing, or replacing system components. Refer to
the Technical Support Information and Downloads website for compatibility information.
This product was evaluated and found to comply with the requirements of NFPA 72, 2010 version, by Factory Mutual.
Figure 1: The EPS shown with the IDNet2 Card

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing