page 13 579-1015 Rev U
4100ES Extended Power Supply Installation Instructions
Troubleshooting
AUX/NAC Terminal
The AUX/NAC terminal block is located on the top right corner of the EPS.
Through the ES Panel Programmer, this point can be configured as either a 24 V auxiliary (AUX) power or as a simple reverse polarity Notification
Appliance Circuit (NAC).
Figure 16: AUX/NAC Terminal
Table 2: AUX/NAC Wiring Specification
Voltage rating: 24 V Special Application
Rating: 2A, maximum.
Wiring gauge: 18 AWG (min.)
to 12 AWG (max.).
Wiring notes:
1. All wiring from the AUX/NAC is power limited.
2. Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3. Terminate Class B NACs as shown using 733- 894. For Canadian applications, mount end-of-line resistor to Simplex-US Model 431537 EOL
plate in accordance with ULC-S527.
4. If circuit is terminated with a 10k EOLR, at the terminals, remove this resistor before wiring.
5. If wiring is routed outside the building, use of a listed secondary protector is required. Use 2081-9028 or 2081-9044. A protector must be
installed at each building exit/entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms wiring resistance, and will
greatly reduce wiring distance.
Figure 17: Simple NAC Wiring
Table 3: NAC Wiring Limits
Alarm Current 20 AWG 18 AWG 16AWG 14 AWG 12 AWG Line Resistance (Ohms)
0.25 617 ft 981 ft 1560 ft 2480 ft 3944 ft 14.00
0.50 308 ft 490 ft 780 ft 1240 ft 1972 ft 7.00
0.75 206 ft 327 ft 520 ft 827 ft 1315 ft 4.67
1.00 154 ft 245 ft 390 ft 620 ft 986 ft 3.50
1.25 123 ft 196 ft 312 ft 496 ft 789 ft 2.80
1.50 103 ft 163 ft 260 ft 413 ft 657 ft 2.33
1.75 88 ft 140 ft 223 ft 354 ft 563 ft 2.00
2.00 77 ft 123 ft 195 ft 310 ft 493 ft 1.75
Note: This Chart indicates the maximum distance for 1/4 -2 A loads. Wiring distance is from the panel terminals to the last appliance. Use of a
2081-9044 protector reduces wiring distance.
Note: