10 — Descripon and Specicaon
a safety hazard to the operator. When a failure occurs, the safety
system immediately removes the load to protect the equipment
from permanent damage.
Table 1 Current draw at specied resolutions (in kilowatts)
150 200 250 300 350
1-phase
208V
721A N/A N/A N/A N/A
240V
625A N/A N/A N/A N/A
3-phase
208V
416A 555A 694A N/A N/A
240V
361A 481A 601A 722A N/A
416V
208A 278A 347A 416A 486A
480V
180A 241A 301A 361A 421A
600V
144A 192A 241A 289A 337A
400 450 500 550 600 650
1-phase
208V
N/A N/A N/A N/A N/A N/A
240V
N/A N/A N/A N/A N/A N/A
3-phase
208V
N/A N/A N/A N/A N/A N/A
240V
962A N/A N/A N/A N/A N/A
416V
555A 625A 694A 763A N/A N/A
480V
481A 541A 601A 662A 722A 782A
600V
385A 433A 481A 529A 577A 626A
ese measurements are based on ideal numbers. ey do not take into account
control power draw, power cable resistance, voltage droop, etc.