Setup — 23
6 SETUP
e Neptune load bank
oers a number of congu-
ration options through its
setup screens. You can access
the setup screens by pressing
“F4 - Setup” or the F4 func-
tion key.
At the main setup screen,
you are presented with four
options:
1. General Settings
2. Automatic Mode Settings
3. Test Mode (Intended only for Simplex engineers)
4. Factory Setup (Intended only for Simplex engineers)
You can access General Settings and Automatic Mode Set-
tings by pressing their respective buttons.
General Settings presents
three elds:
1. Cooldown Delay (sec)
2. Intake Temp Warning (F)
3. Exhaust Temp Alarm (F)
Cooldown Delay deter-
mines how long the load
bank fans will continue run-
ning aer an operation has been concluded. Intake Temp Warn-
ing determines at what temperature the load bank will present a
warning that the air being used for the forced air cooling system
is too hot.
Exhaust Temp Alarm determines how hot the exhaust must
be before the load bank will trigger an Exhaust Temp High alarm
and remove the load. is and Intake Temp Warning may need
to be changed at installation, depending on the climate.
Automatic Mode Settings specify the operation of Automat-
ic/Regenerative Mode. For information about how to set them
up, see “Setting Up Automatic Mode” on page 28.
Neptune load
banks feature
a power
outlet in the
control panel
for your use.
This outlet is
limited to 2
amps.
general
S
ettingS
Cooldown
Delay should
not normally
be changed.
automatiC
m
ode
Figure 19 Setup Screen
Figure 20 General
Settings