DC Inverter Cassette Type Air Conditioner Installation and Operation Manual
71
13. Appendix
Air conditioner nominal working condition and working range:
Test condition
Indoor side Outdoor side
DB(
℃
) WB(
℃
) DB(
℃
) WB(
℃
)
Nominal cooling 27 19 35 24
Nominal heating 20
—
7 6
Rated cooling 32 23 48
—
Low temp cooling 21 15 18(-15)
—
Rated heating 27
—
24 18
Low temp heating 20
—
-7 -8
Note:
● The design of this unit conforms to the requirements of EN14511 standard.
● The air volume is measured at the relevant standard external static pressure.
● Cooling (heating) capacity stated above is measured under nominal working conditions corresponding to
standard external static pressure. The parameters are subject to change with the improvement of products, in
which case the values on nameplate shall prevail.
● In this table, the outdoor side DB temperature of low temp cooling include two values,the one in the
bracket is the working condition of the appliance with function of low temp cooling.