Operation instructions
SIPOS 5 PROFITRON, HiMod
Page 52 Y070.020/GB
6 Parameters and possible parameter values
6
Parameters and possible parameter values
Parameter
Default value
Explanation
Parameter value Other param.
Parameters for maintenance, plant identifi cation number and software functions
Maintenance parameters enable effective planning of valve maintenance intervals depending on the number of starts
performed or the operating hours, for example.
For information on actuator maintenance, refer to section 8 „Maintenance, inspection, service“.
maintenance
Indication is only displayed in the „locPar“ state.
Confi rming with ENTER leads to an update of the maintenance limits and is indicated with
„maintenance – confi rmed!“ for a short time.
confirming
A confi rmation should be entered every time that maintenance has been
done and also whenever the maintenance interval values are changed,
e.g. during initial commissioning.
This resets an applied „maintenance“ signal.
confirmed! The message is only displayed in the „locPar“ state for a short time once
the maintenance has been confi rmed with ENTER.
not necessary The message is only displayed in the „Remote“ state in the „Diagnosis“
menu if none of the possible maintenance limits has been reached.
necessary The message is only displayed in the „Remote“ state in the „Diagnosis“
menu if one of the possible maintenance limits has been reached. In
addition, the „maintenance“ signal is displayed.
maintenance per
E
After pressing the ENTER button, the „switching cycles“, „torque cut-offs“ and „motor oper.hours“
parameters can be changed one after the other. Changes made to the maintenance interval do
not take effect until the „maintenance – confi rming“ parameter has been confi rmed.
switching cycles
Standard: 30.000
Modulating:
10,000,000
Modulating: 30,000 to
30,000,000 by 30,000
each
Standard: 10,000 to
10,000,000
by 100 each
After reaching the programmed number of cycles
the „maintenance“ signal is generated.
torque cut-offs
Standard: 3.000
Modulating:
10,000
Modulating: 200 to
20000 by 200
each Standard: 100 to
10000 stufenweise by
100 each.
After reaching the programmed number of torque-
dependent cut-offs, the „maintenance“ signal is
generated.
motor oper.hours
2,500
5 h to 2500 h by 5
each.
After reaching the programmed number of motor
operation hours, the „maintenance“ signal is
generated.
return to menu Return to „maintenance per.“ parameter
actuat.Tag 1-10
Actuator plant identifi cation number , used for plant identifi cation.
Entry: Use the
and buttons to select alphanumerical characters and confi rm with ENTER. The
next data digit blinks and can be programmed.
Exit setting menu: Press ENTER after entering position 10. Change-over to the next function:
Press
or
buttons.
actuat.Tag 11-20
See actuat. Tag 1-10.
Optional software functions
The software functions listed in the following are already included in the actuator if they were part
of the order. The software functions can also be released at a later date. Each software function
requires a PIN code which is available as an accessory (also refer to the following chapter
„Optional software functions“).
The operation sequence for enabling the software functions is always the same and therefore
described as an example for the following software function.
enable ProcCntr
„Process controller“
enabled Function is enabled.
disabled Function is disabled. Press ENTER to enable the function.
enable ProcCntr
0000
Enter enable code in the same way as the code for
access authorization, chapter 5.3.