8 Operation
SMA Solar Technology AG
Operating manualEDMM-10-BE-en-2042
8.5 Configuring Modbus Devices
Connected Modbus devices can be used, for example, as energy meters for generation and
consumption data at the grid-connection point or for energy monitoring. For this, predefined
Modbus profiles, user-created Modbus profiles or the SunSpec Modbus profile must be used. The
Modbus profiles will then be assigned to the Modbus devices.
IP addresses of Modbus devices
In systems with Modbus devices, static IP addresses must be assigned to all Modbus devices.
Suitable IP addresses can be assigned to the Modbus devices from the free address supply of
the network segment either manually or dynamically via DHCP.
If the IP addresses are to be assigned dynamically, DHCP must be activated in the router (see
the router manual). Make sure that the Modbus devices do not contain variable IP addresses
but always the same IP addresses.
Creating a New Modbus Profile
1. Log into the user interface of the DataManager.
2. Select the Device registration menu item in the Configuration menu.
3. Select the button Configuration in the Modbus devices row.
4. Select Manage your own Modbus profiles.
5. Select Create a new Modbus profile.
6. Fill out the entry fields and select [Save].
Registering a New Modbus Device and Assigning a Modbus Profile
Requirement:
☐ The Modbus devices must be in operation and connected to the Data Manager.
Procedure:
1. Log into the user interface of the DataManager.
2. Select the Device registration menu item in the Configuration menu.
3. Select the button Configuration in the Modbus devices row.
4. Select the button to register a new Modbus device.
5. Fill out the entry fields and select [Save].
☑ The connected Modbus energy meter can be used as an energy meter for generation and
consumption data at the grid-connection point or for energy monitoring.
SunSpec Modbus Profile
The product provides Modbus profiles for SunSpec Modbus. The connected Modbus devices must
conform with the SunSpec specification (see manufacturer manual). The mandatory data of the
following SunSpec models are supported:
Common model:
• 1, 11, 12