6 Connecting the Sunny Home Manager SMA Solar Technology AG
20 FSS-IS-en-42 Installation Manual - Quick Reference Guide
6 Connecting the Sunny Home Manager
Figure6: Connecting the Sunny Home Manager
Requirements:
All Speedwire devices must be connected to the same router.
The router and the optional network switch must fully support Multicast.
The router must support "Internet Enabled Devices" with the interfaces SIP and STUN.
The most common routers and network switches support Multicast and "Internet Enabled Devices".
Position Designation Description / information
A AC power cable Terminal AC2 Gen/Grid, terminals L, N
TT
und PE
Utility grid connection with a three-wire cable
Connect slave 1 to line conductor L2, connect slave 2 to line conductor L3.
Conductor cross-section: 6 mm² to 16 mm²
B Grounding conductor Terminal AC1 Loads/SunnyBoys, terminal PE
Additional grounding if the conductor cross-section of the AC power cable
is less than 10 mm².
The conductor cross-section must equal at least the conductor cross-section
of the AC power cable.
C DC+ cable Battery terminal
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm
Torque: 12 Nm
D DC − cable
E Data cable for the internal
communication in the cluster
Terminal ComSync In
With slave 1: connection of internal communication bus of master
With slave 2: connection of internal communication bus of slave 1
F Data cable for the internal
communication in the cluster
Terminal ComSync Out
With slave 1: connection of internal communication bus after slave 2
With slave 2: leave terminator plugged in. Slave 2 is connected to slave 1
only.