SMA Solar Technology AG 7 Commissioning
Installation Manual - Quick Reference Guide FSS-IS-en-42 25
7.2 Adjusting the Configuration of the Sunny Island Inverter
7.2.1 Countries in Which the Configuration Must Be Adjusted
In the SMA Flexible Storage System, the Sunny Island inverters are connected to the utility grid and must meet the
requirements of the grid operators. Depending on the settings, the Sunny Island inverters fulfill the requirements of the
application guide VDE-AR-N 4105:2011-08 or AS4777. The standard country data set of the Sunny Island inverters is
set to VDE-AR-4105 or AS4777 by default. The configuration must be adjusted for the following countries
(status: July 2014):
Denmark (see Section7.2.2, page25)
Austria(see Section7.2.3, page26)
Switzerland(see Section7.2.4, page26)
The configuration may only be adjusted on request or with permission of the grid operator in the following countries
(status: July 2014):
•Australia
Country data set: AS4777
•Belgium
Country data set: VDE-AR-4105
•Germany
Country data set: VDE-AR-4105
Use in other countries is possible with the agreement of the grid operator. Consult the grid operator on whether
adjustment is necessary.
7.2.2 Adjusting the Configuration for Denmark
When using the Sunny Island inverter 6.0H / 8.0H in Denmark, you must reduce the discharge/charging current
(default setting: max. 20.0 A).
When using the Sunny Island inverter 3.0M / 4.4M in Denmark, you can retain the default setting of the discharge/
charging current (default setting: max. 16.0 A).
Requirements:
The extended configuration must be performed within the first ten operating hours of the Sunny Island inverter,
otherwise an SMA Grid Guard code is required in order to change grid-relevant parameters (application form for
the SMA Grid Guard code available at www.SMA-Solar.com).
The country data set of the Sunny Island inverter must be set to VDE-AR-4105 (see Section7.1 "Basic Configuration
of the Sunny Island Inverter", page21).
Procedure:
1. Log in to the communication product as Installer (see the user manual of the communication product) or switch to
expert mode on the Sunny Remote Control (see the Sunny Island operating manual).
2. Set the parameter Maximum AC battery charging current or 210.03 InvChrgCurMax to 16,0 A.