7 Commissioning SMA Solar Technology AG
24 FSS-IS-en-42 Installation Manual - Quick Reference Guide
If the country data set of the Sunny Island inverter is
VDE-AR-4105, set the type of feed-in for the PV system
(see Section3.1, page10).
If the country data set of the
Sunny Island inverter is
AS4777, confirm the basic
configuration with Y.
Confirm the basic
configuration with Y.
Asymmetric: The
installation site is located in
Germany and at least one PV
inverter feeds in
asymmetrically on a single
line conductor.
Symmetric: The installation
site is either located outside
of Germany or all
PV inverters feed in
symmetrically on three line
conductors.
Wait until the upper LED
(inverter LED) on slave 1 is
flashing and the Sunny
Remote Control is displaying
To identify Slave1, press
Tss on the Slv.
Set the line conductor
to which the
Sunny Island
is connected:
Confirm the basic
configuration
with Y.
Press the start-stop button
on slave 1.
L1: connection to line
conductor L1
L2: connection to line
conductor L2
L3: connection to line
conductor L3
Confirm the basic
configuration with Y.
Wait until the upper LED
(inverter LED) on slave 2 is
flashing and the Sunny
Remote Control is displaying
To identify Slave2, press
Tss on the Slv.
Press the start-stop button
on slave 2.
☑ The basic configuration is complete.
If an SD memory card is inserted in the Sunny Remote Control, the message
Do not remove MMC/SD memory card ... appears.
Close the circuit breaker F1 and the residual-current device F2 in the distribution board and leave the Sunny Island
switched on, but do not start it.