8 Commissioning
SMA Solar Technology AG
Operating Manual 47HS-BM-3.28-10-BE-en-10
8.5 Checking the configuration of the battery modules in the installation
assistant
The user interface available and its functions depend on the inverter. The procedure is described here as an example.
Refer to the inverter user manual for detailed information.
The installation assistant leads you step-by-step through the steps necessary for the initial configuration of the inverter
including the battery modules.
Figure 19: Layout of the installation assistant (example)
Position Designation Description
A Configuration steps Overview of the installation assistant steps. The number of steps de-
pends on the type of device and the additionally installed modules.
The current step is highlighted in blue.
B User information Information about the current configuration step and the setting op-
tions of the configuration step.
C Configuration field You can make settings in this field.
Procedure:
1. Activate the user interface of the inverter.
2. Log in as Installer.
3. Select the menu User settings on the home page of the user interface.
4. In the context menu, select [Starting the installation assistant].
☑ The installation assistant will open.
5. Follow the installation assistant steps up to the Battery configuration. For every setting made in a step, click on
[Next].
6. Check whether the Current capacity shown in the inverter user interface matches the usable energy capacity
indicated in this manual.
7. If the two specifications regarding battery capacity do not match, disconnect the inverter from voltage sources,
ensure that all battery cables are property connected and recommission the inverter.
8. If the two specifications regarding battery capacity still do not match, contact Service.