6 Electrical Connection
SMA Solar Technology AG
Installation Manual 35PPM-10-IA-en-16
Terminal Switching input
or output
Function Designation
X702:15 DIO8 Feedback of circuit breaker of the utility grid: If the
contact is closed, the utility grid is connected to the
local utility grid.
-
X702:16
X702:17 DIO9 Feedback of circuit breaker of genset 7: If the con-
tact is closed, the genset is operating and connected
to the local utility grid.
-
X702:18
X702:19 DIO10 Feedback of circuit breaker of genset 8: If the con-
tact is closed, the genset is operating and connected
to the local utility grid.
-
X702:20
X702:21 DIO11 Only usable with synchronization assembly: Feed-
back circuit breaker
-
X702:22
X702:23 DIO12 Only usable with synchronization assembly: Reserve -
X702:24
X703:1 DIO13 Indicator light "Operation" Change-over con-
tact
X703:2 Make contact
X703:3 Break contact
X703:4 DIO14 Indicator light "Warning" Change-over con-
tact
X703:5 Make contact
X703:6 Break contact
X703:7 DIO15 Multifunctional output: In the default configuration,
no function is selected.
Change-over con-
tact
X703:8 Make contact
X703:9 Break contact
X703:10 DIO16 Multifunctional output: In the default configuration,
no function is selected.
Change-over con-
tact
X703:11 Make contact
X703:12 Break contact
X703:13 DIO17 Only usable with synchronization assembly: Circuit
breaker On
Change-over con-
tact
X703:14 Make contact
X703:15 Break contact