EasyManua.ls Logo

SMA PPM-10 - Supply Voltage Connection

SMA PPM-10
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical Connection
SMA Solar Technology AG
Installation Manual 31PPM-10-IA-en-16
Position Designation Description
C Power analyzer with measuring
module K103
Current and voltage measurement
The terminal block X700 is intended for one current measurement.
The terminal block X200 is intended for one voltage measurement.
D
Synchronization assembly K104
Synchronization
The terminal block X700 is intended for one current measurement.
The terminal block X200 is intended for the two voltage measure-
ments.
The terminal block X703 is intended for the circuit breakers.
The terminal block X702 is intended for the connection of the feed-
back contacts.
6.2 Connecting the Supply Voltage
The product offers several options for voltage supply. Depending on the ordered version, you use 1 of these options:
Terminal of AC supply voltage (230 V AC)
Terminal of DC supply voltage (24 V DC or 48 V DC or 110VDC)
Note the information on the type label of the product.
Requirements:
The supply voltage must be protected by an external miniature circuit breaker type B16A or by an external
branch circuit breaker in accordance with local laws, regulations, codes and standards (e.g. National Electrical
Code® ANSI/NFPA70 or Canadian Electrical Code® CSA-C22.1.).
In TT systems, the supply voltage must be additionally protected by means of a residual-current device.
When a DC supply voltage is connected, the negative terminal of the DC supply voltage must be grounded.
Cable requirements:
Number of insulated conductors: 3 (incl. grounding conductors)
Conductor cross-section for rigid cables: 1.5mm² to 4mm² (16AWG to 12AWG)
Conductor cross-section for flexible cables: 1.5mm² to 2.5mm² (16AWG to 14AWG) (when using bootlace
ferrules)
The cable must also include a grounding conductor.
The cable must be suitable for the local grid voltage and external fusing.

Table of Contents

Related product manuals