6 Electrical Connection
SMA Solar Technology AG
Installation Manual 37PPM-10-IA-en-16
The block circuit diagrams introduced in this section, describe the connection of the inputs for the current and voltage
measurement using the example of current measurement1, current measurement2 and voltage measurement1. The
same block circuit diagrams apply to all other current and voltage measurements.
Block circuit diagram for 4-conductor utility grid with 3 line conductors and 1 neutral conductor
L1
L2
L3
X700
1 2
k1 l1
3 4
k2 l2
5 6
k3 l3
7 8
k4 l4
9 10
k5 l5
11 12
k6 l6
13
lx
* * * * * *
L1
L2
L3
N
L1
L2
L3
N
N
Current measurement 1 Current measurement 2
Hybrid-grid connection
Load 1 connectionLoad 2 connection
* Remove jumper on the wired terminals of the connecting terminal plate X700.
Figure 19: Current measurement within the 4-conductor utility grid (example)
L1
L2
L3
1 2
L1 L2
3 4
L3
N
5
PE
X200
L1
L2
L3
1 2
L1 L2
3 4
L3
N
5
PE
X200
N
N
*
Voltage measurement 1Voltage measurement 1
* If measured with voltage converter, use for the selected voltage measurement at the connecting terminal plate X200 the red jumper between N and PE.
Figure 20: Voltage measurement within the 4-conductor utility grid (example): with and without voltage converter