6 Electrical Connection
SMA Solar Technology AG
Installation ManualPPM-10-IA-en-1642
Measur-
ing mod-
ule
Current
Mea-
sure-
ment
Variant Current transformer Terminal cur-
rent trans-
former
Terminal
product
K105 5 HybridController L L1 k1 X700:29
l1 X700:30
L2 k2 X700:31
l2 X700:32
L3 k3 X700:33
l3 X700:34
6 HybridController L L1 k4 X700:35
l4 X700:36
L2 k5 X700:37
l5 X700:38
L3 k6 X700:39
l6 X700:40
5 and 6 HybridController L N and internal neutral
point of the current trans-
formers
lx X700:41
Do not connect the termi-
nal. Internal use
X700:42
Requirements:
The connected local utility grid must be a 4-conductor or a 3-conductor utility grid according to its grid type. If
another grid type is used, the connection of the current transformers must be coordinated with
SMASolarTechnologyAG.
Only 1 grid type must be connected per measuring module.
The cables must be protected in accordance with the locally applicable standards and directives.
The current transformers used must have at least accuracy class 1.
The nominal output power of the current transformer must be at least 2.5VA.
The outputs of the current transformers are already grounded within the product. Therefore, the outputs of the
current transformers must not be grounded in any way outside of the product.
It must be possible to short-circuit the current transformer outputs by an external short circuit device outside of the
product.
Summation current transformers must have identical transformation ratios and be of the same type.
When using summation current transformers, the entire current transformer system must have the resulting
accuracy class 1 or lower.
The requirements for the measurement inputs of the product must be complied with (see Section10, page63).
When the power analyzer is used with measuring modules, the current transformers used must have a secondary
rated current of 1A (variants: Hybrid Controller L / Hybrid Controller XL 1xGMP / Hybrid Controller XL 2xGMP).