6 Electrical Connection
SMA Solar Technology AG
Installation ManualPPM-10-IA-en-1644
NOTICE
Destruction of the measuring module due to short circuit
If a voltage-measurement device is connected to a measuring module in a 4-conductor utility grid, and a voltage
converter is not interconnected, there must not be a conductive connection between the neutral conductor and
grounding conductor. A conductive connection between the neutral conductor and the grounding conductor may
occur by inserting a jumper and then can result in a short circuit during commissioning. The measuring module is
destroyed when a short circuit occurs.
If a voltage-measurement device without a voltage converter is connected to measuring module 1 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:4 and X200:5 has been removed.
If a voltage-measurement device without a voltage converter is connected to measuring module 2 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:9 and X200:10 has been removed.
If a voltage-measurement device without a voltage converter is connected to measuring module 3 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:14 and X200:15 has been
removed.
Terminal assignment:
Measuring
module
Voltage mea-
surement
Available with option Conductor Terminal on product
K103 1 HybridController L
Hybrid Controller XL 1xGMP
Hybrid Controller XL 2xGMP
Hybrid Controller XL Synch
Line conductor L1 X200:1
Line conductor L2 X200:2
Line conductor L3 X200:3
Neutral conductor N X200:4
Grounding conductor
PE
X200:5
K104 2 HybridController L
Hybrid Controller XL 2xGMP
Hybrid Controller XL Synch
Line conductor L1 X200:6
Line conductor L2 X200:7
Line conductor L3 X200:8
Neutral conductor N X200:9
Grounding conductor
PE
X200:10
K105 3 HybridController L
Hybrid Controller XL Synch
Line conductor L1 X200:11
Line conductor L2 X200:12
Line conductor L3 X200:13
Neutral conductor N X200:14
Grounding conductor
PE
X200:15
Requirements:
The connected local utility grid must be a 4-conductor or a 3-conductor utility grid according to its grid type. If
another grid type is used, the connection of the current transformers must be coordinated with SMA Solar
Technology AG.