10 Technical Data
SMA Solar Technology AG
Installation Manual 65PPM-10-IA-en-16
Multifunctional switching inputs and switching outputs
Connectable switches Potential-free switches
Type of connection Spring-cage terminal
Conductor cross-section 1.5mm² to 2.5mm²
Voltage measurement inputs HybridController L HybridController XL
Maximum number of voltage measurement inputs 3 1 to 3*
Compatible power analyzers Yes (in acc. with IEC 60664-1)
Type of the voltage measurement inputs Three-phase
Measurement range of the voltage measurement be-
tween line conductor and neutral conductor
100V to 277V
Measurement range of the voltage measurement be-
tween line conductor and line conductor
170V to 480V
Impedance of the voltage measurement >2MΩ per line conductor
* The maximum number of voltage measurement inputs depends on the variant ordered (HybridControllerXL1xGMP /
HybridControllerXL2xGMP / HybridControllerXLSynch)
Current measurement inputs HybridController L HybridController XL
Maximum number of current measurement inputs 6 1 or 2*
Compatible power analyzers Janitza UMG 604, SMA FSC-11-DAQ
Type of the current measurement inputs Three-phase
Current measurement range 0A to 1A
Power consumption of the current measurement internal
resistor
<100mVA
Minimum nominal output power of the current transform-
ers
2.5VA
Type of connection Spring-cage terminal
Conductor cross-section 1.5mm² to 2.5mm²
Maximum cable length 100m
Overvoltage category as per IEC 60664-1 III
* The maximum number of current measurement inputs depends on the variant ordered (HybridControllerXL1xGMP /
HybridControllerXL2xGMP / HybridControllerXLSynch)
Tolerances of the measuring modules of simple current and voltage measurement and synchronization
Voltage measurement (reference value: nominal voltage
of the measuring module)
-0.1% to +0.1%
Current measurement (reference value: nominal current
of the measuring module)
-0.3% to +0.3%