Mounting SMA America, LLC
26 SB50US-80US-eng-IUS112633 Installation Guide
5.2 Requirements for the Mounting Location
Observe the following conditions during installation:
The installation method and mounting location must be suitable for the weight and dimensions
of the Sunny Boy (see section 11 ”Technical Data” (page 88)).
Note the dimensions of the DC Disconnect (Page 32).
Mount the inverter on a stable surface.
The mounting location must be accessible at all times.
Mount vertically or tilted backward at max. 45°.
The connection area must point downward.
Do not install the inverter tilting forward.
Do not install the inverter horizontally.
Install the inverter at eye level in order to be able to read out the operating state at any time.
The ambient temperature must be below +113 °F (+45 °C).
Do not expose inverter to direct sunlight.
In the living area, do not install inverters on a
plasterboard wall or similar wall.
The Sunny Boy may emit noises when in use which
can be regarded as a nuisance.