SMA America, LLC Electrical Connection
Installation Guide SB50US-80US-eng-IUS112633 47
6.5 DC Wiring
DANGER
High voltages in PV modules exposed to light.
Risk of death due to electric shock from touching a DC conductor.
During installation, cover the PV modules with opaque material.
DANGER
High voltages in the DC cables.
Risk of death or serious injury from touching a DC cable.
Only connect the DC cable from the PV module to the inverter as described in this
manual.
NOTICE
Potential damage to the inverter due to overvoltage.
The DC input voltage of the PV modules must not exceed the maximum values of the
inverter. Observe the information on the type label.
Check the polarity and the open-circuit voltage of the PV strings before connecting
the DC cables to the inverter.
Configure the DC input voltage range accordingly before connecting the PV modules
to the inverter.Use "Sunny Design" on www.SMA-America.com for string
configuration.