Electrical Connection SMA America, LLC
38 SB50US-80US-eng-IUS112633 Installation Guide
6.2 Opening the Sunny Boy
1. Switch off all AC and DC breakers or switch-disconnectors. Ensure they cannot reconnect
accidentally.
2. Wait at least 5 minutes until the residual voltage has been drained.
3. Remove the 6 screws and conical spring washers from the enclosure lid. Pull the lid forward
smoothly.
4. Put the cover, screws and washers aside.
The Sunny Boy is open.
DANGER
High voltages are present in the Sunny Boy during operation.
Death or serious injury due to electric shock.
Only open the Sunny Boy in the order described as follows.
NOTICE
There may be an ingress of moisture into the open Sunny Boy.
Potential damage to the Sunny Boy.
Do not open the Sunny Boy in the event of rain or a high level of humidity (> 95 %).
Handle the enclosure lid with care.
The seal of the enclosure may become frozen shut due to frost.
Potential damage to the seal when opening the Sunny Boy.
Do not open the Sunny Boy when the outdoor temperature is below 23 °F ( 5 °C).