6 Maintenance
SMA Solar Technology AG
Maintenance Manual 55SCCPXT-E7-WA-en-37
Remove the grounding conductor from the inverter.
Remove the roof and set it down on a suitable surface.
Clean air intake with a vacuum cleaner
Place the roof on the inverter.
Screw the grounding conductor to the inverter (torque: 14.2Nm).
9. Slide the roof into the guide rails on the inverter and pull forward.
10. Press the roof down.
11. Mount the ventilation grids (see Section7.1.3, page64).
6.4.2.5 Cleaning the Interior
DANGER
Danger to life due to electric shock or electric arc if live components are touched
Switch off the inverter and wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
Disconnect the inverter (see Section4, page26).
Procedure:
1. Remove dirt and dust from the inverter interior and from all devices.
2. Check the inverter for leaks.
If leaks are present, fix them.
3. Remove moisture.