EasyManua.ls Logo

SMA SUNNY CENTRAL 900CP XT - Repair Work; Reading off the Replacement Interval Meter

SMA SUNNY CENTRAL 900CP XT
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Maintenance
SMA Solar Technology AG
Maintenance Manual 61SCCPXT-E7-WA-en-37
Position Material number Designation
G 86-0043553 Risk of lethal electric shock due to active power source
H 86-003307 5 Safety rules
I 86-1086701026 The negative pole of the PV generator is grounded in the inverter.
86-1086701027 The positive pole of the PV generator is grounded in the inverter.
K 86-003304 Unintended tripping due to modified settings.
L 86-003306 Plant protected by conductors.
M 86-003305 Incorrect connection leads to destruction of the device.
N 86-1086701023 Risk of lethal electric shock due to active power source
O 86-0099 Position of grounding
P 86-1086701024 Danger of burn injury due to hot components below the cover.
Q 86-10867153 Risk of electrical shock even when the device is disconnected.
DANGER
Danger to life due to electric shock or electric arc if live components are touched
Switch off the inverter and wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
Disconnect the inverter (see Section4, page26).
Procedure:
Check whether any warning message or label is damaged or missing.
Replace any warning messages and labels which are missing or illegible. If necessary, you can order labels as a
complete set. Contact us (see Section9, page68).
6.5 Repair Work
6.5.1 Reading off the Replacement Interval Meter
1. Log into the user interface as an installer (see Section7.4.1, page66).
2. Select Data > Devices.
3. Select the desired device from the list.
4. Select the tab Instantaneous values.
5. If the instantaneous value CntGfdiSw exceeds 7000, replace the RemoteGFDI (see Section9 "Contact",
page68).
6. If the error message 7714 appears on the touch display, replace the GFDI (see Section9 "Contact", page68).

Table of Contents