SMA Solar Technology America LLC 19 Parameter Lists
Operating Manual SI4548-6048-US-BE-en-21 167
145# SIC50 4
19.2 Adjustable Parameters
19.2.1 Inverter Settings (210#)
08 Sic3SWVers Software version of the third Sunny Island Charger
No. Name Description
01 Sic4EgyCntIn Energy of the fourth Sunny Island Charger in kWh
02 Sic4TdyEgyCntI
n
Daily yield of the fourth Sunny Island Charger in kWh
03 Sic4PvPwr PV power of the fourth Sunny Island Charger in W
04 Sic4PvVtg PV voltage of the fourth Sunny Island Charger in V
05 Sic4BatVtg Battery voltage of the fourth Sunny Island Charger in V
06 Sic4BatCur Battery current of the fourth Sunny Island Charger in A
07 Sic4HsTmp Heat sink temperature of the fourth Sunny Island Charger in °C
08 Sic4SWVers Software version of the forth Sunny Island Charger
No. Name Description Value Explanation Default
value
01 InvVtgNom Nominal voltage of
the Sunny Island
120 V / 60 Hz 120 V
02 InvChrgCurMax Maximum AC
charging current
SI 4548-US-10 37.5 A
SI 6048-US-10 48 A
03 InvFrqNom Nominal frequency
of the Sunny Island
120 V / 60 Hz 60 Hz
No. Name Description