SMA Solar Technology America LLC 19 Parameter Lists
Operating Manual SI4548-6048-US-BE-en-21 173
232# Grid Control
No. Name Description Value Explanation Default
value
01 GdVtgMin Minimum grid voltage 105.6 V
02 GdVtgMax Maximum grid voltage 132 V
03 GdCurNom Nominal grid current 30 A
04 GdFrqNom Nominal grid
frequency
60 Hz
05 GdFrqMin Minimum power
frequency
59.3 Hz
06 GdFrqMax Maximum power
frequency
60.5 Hz
07 GdVldTm Minimum time required
for grid (voltage and
frequency) to be within
permissible range for
connection
300 sec
08 GdMod Grid interface GridCharge Charging on the
utility grid
GdFeed
GridFeed Charge and
feedback on the
utility grid
09 GdRvPwr Permissible grid reverse
power (active power)
0 W to 5,000 W 100 W
10 GdRvTm Permissible time for
grid reverse power
0 sec to 60 sec 5 sec
15 GdAlSns AI sensitivity Low Low Normal
Medium Medium
Normal Normal
High High
37 GdVtgIncProEna Voltage increase
protection
Disable Disable Disable
Enable Enable
38 GdVtgIncPro Limit for voltage
increase protection
132 V
41 GdSocEna Activate the grid
request based on SOC
Disable Disable Disable
Enable Enable