SMA Solar Technology America LLC 19 Parameter Lists
Operating Manual SI4548-6048-US-BE-en-21 183
242# Relay Load
07 ExtPwrDerMinT
m
Minimum time of
external power
reduction
0 min to
600 min
10 min
08 ExtPwrDerDltVtg Differential voltage
of external power
reduction
0 V to 0.4 V 0.15 V
No. Name Description Value Explanation Default
value
01 Lod1SocTm1Str SOC limit for load
shedding 1 start for t1
30%
02 Lod1SocTm1Stp SOC limit for load
shedding 1 stop for t1
50%
03 Lod1SocTm2Str SOC limit for load
shedding 1 start for t2
30%
04 Lod1SocTm2Stp SOC limit for load
shedding 1 stop for t2
50%
05 Lod1Tm1Str Time 1 for Loadshed 1
in hours, minutes and
seconds
Start: time 1, end: time
2
06 Lod1Tm2Str Time 2 for Loadshed 1
in hours, minutes and
seconds
Start: time 2, end: time
1
07 Lod2SocTm1Str SOC limit for load
shedding 2 start for t1
30%
08 Lod2SocTm1Stp SOC limit for load
shedding 1 stop for t2
50%
09 Lod2SocTm2Str SOC limit for load
shedding 2 start for t2
30%
10 Lod2SocTm2Stp SOC limit for load
shedding 2 stop for t2
50%
No. Name Description Value Explanation Default
value