HGM1780 Automatic Genset Controller
HGM1780 Automatic Genset Controller
Crank
Disconnect
Condition
Starter motor disconnection
condition. There are 3 conditions of
disconnecting starter with engine.
Each condition can be used alone
and simultaneously to separating
the start motor and genset as soon
as possible.
When generator speed higher than
the set value, starter will be
disconnected.
Disconnect
Generator
Freq
When generator frequency higher
than the set value, starter will be
disconnected.
When generator oil pressure higher
than the set value, starter will be
disconnected.
SGD (120ºC resistor type)
SGD (10Bar resistor type)
Not used. (If fuel level sensor is
used, then the digital input port
must be set as „not used‟.
0: Warn; 1: Shutdown; 2:Trip