HGM400N Series Genset Controller User Manual Page 22 of 38
High Temp. Inhibit
Enabled
Factory default: when high temperature occurs,
shutdown alarm is initiated. NOTE 2
Factory default: when low oil pressure occurs,
shutdown alarm is initiated. NOTE 3
Factory default: when low fuel level occurs,
shutdown alarm is initiated. NOTE 4
Factory default: when config. sensor value
higher/lower than the set value (particular case
depends on the sensor type), warning alarm is
initiated. Functions see 66, 67, 68.
0: 3P4W; 1: 2P3W
2: 1P2W; 3: 3P3W
Multiplex Input Level
Sensor
0: Digital Input 3
1: Level Sensor
Please see Table 8. NOTE 5
Multiplex Input Config.
Sensor
0: Digital Input 4
1: Temperature Sensor
2: Oil Pressure Sensor
3: Level Sensor
Please see Table 8. NOTE 5
Number of generator poles. It can be used for
calculating engine speed which without speed
sensor.
0: Indication (Corresponding sensor position
on the LCD will show “+++”);
1: Warn; 2: Shutdown
Fuel Level Sensor Open
Action
Config. Sensor Open
Action
It controls the cooling blower to open or close
if the output port is configured as Cooling
Blower.
When the fuel level of the external sensor falls
below the set value, “Low Fuel Level” timer is
initiated. (this only concerns fuel level sensor
and does not concern low fuel level warning