genset will take load; generator power indicator will illuminate and generator will enter 
into Normal Running status. if voltage or frequency is abnormal, the controller will 
initiate shutdown alarm (alarm information will be displayed on LCD). 
9. 
In case of running in parallel, after the warming up delay: 
a) 
If bus has no voltage, then the controller will send a closing signal to other waiting 
parallel gensets and generator close relay will activate, this prevents other sets in the 
system from attempting to close their own breakers at the same time. 
b) 
If bus has voltage or other gensets are already closed, the controller will adjust speed 
and  voltage  through GOV  and  AVR  to  synchronize the  gensets  to  the  bus; when 
synchronism requirements has been achieved, breaker close signal will be initiated 
and the genset will be paralleled with the bus. Once they are paralleled, the controller 
will control the generator to gradually accelerate and share load with other paralleled 
gensets. 
Automatic Stop Sequence, 
1) 
When the “Remote Start” signal is removed, the Stop Delay is initiated. 
2) 
Once this “stop delay” has expired, the module will ramp the load from the generator 
to remaining set. The Generator Breaker will open and the “Cooling Delay”  is then 
initiated.  Should  the  Remote  Start  signal  be  re-activated  during  the  cooling  down 
period, the set will return parallel status. Once the “Cooling Delay” expires, the “Stop 
Idle” delay is initiated. 
3) 
During “Stop Idle” Delay (if configured), idle relay is energized. If the unit has been 
configured for CAN Bus, stop command can be carried out via CAN Bus; 
4) 
“ETS Solenoid Hold” begins, ETS relay is energized while fuel relay is de-energized. 
5) 
"Fail to Stop Delay" begins, complete stop is detected automatically. 
6) 
Generator is placed into its standby mode after its complete stop. Otherwise, fail to 
stop alarm is initiated and the corresponding alarm information is displayed on LCD. 
5.2  MANUAL OPERATION (MULTIPLE SETS) 
 
1. 
Manual  mode  is  selected  by  pressing  the  button;  a  LED  besides  the  button  will 
illuminate to confirm the operation; then press   button to start the gen-set; 
2. 
Preheat  relay energizes  (if  configured), “preheat  delay XX s”  information  will    be 
displayed on LCD; 
3. 
After the above delay, the Fuel Relay (or ECU output if configured) is energised, and 
then one second later, the Start Relay is engaged. The engine is cranked for a pre-
set time. If the engine fails to fire during this cranking attempt then the fuel relay and 
start relay are disengaged for the pre-set rest period; “crank rest time” begins and 
wait for the next crank attempt.