12.2  STEP 2: MANUAL PARALLEL OPERATION OFF-LOAD 
 
1) 
Close breaker and parallel gensets manually, check that the units synchronization 
parallel is smooth and steady and breaker close impulse current is not too high; 
2) 
After gensets parallel operation off load, check that there is no high circumfluence on 
HGM6510 current screen; 
3) 
After gensets parallel operation off load, check if the output of active and reactive 
power is equal to 0; if it is not, then check if there is power oscillation; if there is, 
adjust the gain and stability values of HGM6510 controller, or adjust engine GOV or 
generator AVR gain and stability potentiometer to avoid active and reactive power 
oscillation; output is close to 0. 
 
12.3  STEP 3: MANUAL PARALLEL OPERATION ON-LOAD 
 
1) 
Parallel the gensets manually, perform on-load test and check if active and reactive 
power is evenly distributed between all the gensets; 
2) 
Parallel  the  gensets  manually,  perform  ramp  on-load  test  to  see  if  there  is  high 
overshoot or power oscillation during this period; if there is, regulate Load Rampx%/s 
via PC software; 
3) 
Parallel the gensets and on-load manually, perform ramp off-load test to see if gen-
set breaker opens after reaching minimum load threshold (%); 
4) 
Parallel the gensets manually, perform impact load test and impact off-load test to 
check if there is power oscillation. 
 
12.4  STEP 4: FULLY AUTOMATIC PARALLEL OPERATION 
 
When the controller is  in auto mode,  if  “remote  start on-load demand”  is active, it will 
carry  out  fully  automatic  parallel  operation,  start  and  stop  according  to  the  users’ 
requirement. There are 3 ways of automatic parallel operation: 
1) 
Start on-load demand: the module with the highest priority starts firstly. When load 
exceeds the pre-set start maximum percentage, the second according to the priority 
module will start the gen-set, synchronize and share load. When load falls lower than 
the preset minimum stop percentage, after stop delay the second module breaker will 
be open and the module will be cooled down and stopped. 
2) 
Start all sets initially: all the modules start at the same time; the first module to reach 
load  condition  closes  first;  when  other  modules  reach  load  condition,  they 
synchronize one by one. After that the modules monitors the load; If load value   falls