Model
Flow range [L/min]
−5 0 5 10 25 50 100
PF2M701(-L)
PF2M702 (-L)
PF2M705 (-L)
PF2M710 (-L)
PF2M725 (-L)
PF2M750 (-L)
PF2M711(-L)
Min. value of
the rated flow
Flow
Zero cut-off
range
Max. value of
the rated flow
C
D
B
A
0
Min. value of
the rated flow
Flow
Zero cut-off
range
Max. value of
the rated flow
G
H
F
E
0
Output
Output
Rated flow range Set point range Display range
Set Point Range and Rated Flow Range
10.0 L/min (5 L/min)0.1 L/min
−0.5 L/min 10.5 L/min (5.25 L/min)
−0.5 L/min 10.5 L/min (5.25 L/min)
1.0 L/min (0.5 L/min)0.01 L/min
−0.05 L/min 1.05 L/min (0.525 L/min)
−0.05 L/min 1.05 L/min (0.525 L/min)
2.0 L/min (1 L/min)0.02 L/min
−0.1 L/min 2.1 L/min (1.05 L/min)
−0.1 L/min 2.1 L/min (1.05 L/min)
0.3 L/min 25.0 L/min (12.5 L/min)
−1.3 L/min 26.3 L/min (13.1 L/min)
0.05 L/min 5.0 L/min (2.5 L/min)
−0.25 L/min 5.25 L/min (2.63 L/min)
−0.25 L/min 5.25 L/min (2.63 L/min)
1 2
Set the flow rate within the rated flow range.
The set point range is the range of flow rate that can be set in the switch.
The rated flow range is the range that satisfies the switch specifications (accuracy, linearity, etc.).
It is possible to set a value outside of the rated flow range if it is within the set point range, however, the satisfaction of specifications can
not be guaranteed. The flow range if using CO2 is given in brackets.
−5.0 L/min
105.0 L/min
(52.5 L/min)
−5.0 L/min
105.0 L/min
(52.5 L/min)
100.0 L/min
(50 L/min)
1.0 L/min
52.5 L/min (26.3 L/min)−2.5 L/min
52.5 L/min (26.3 L/min)−2.5 L/min
50.0 L/min (25 L/min)0.5 L/min
26.3 L/min (13.1 L/min)−1.3 L/min
Flow/Analog Output
A
B
C
PF2M701/02/05
/10/50/11(-L)
PF2M725 (-L)
Voltage output (1 to 5 V) 1 V 1.04 V 1.05 V 5 V
Current output (4 to 20 mA) 4 mA 4.16 mA 4.19 mA 20 mA
E
F
G
PF2M701/02/05
/10/50/11(-L)
PF2M725 (-L)
Voltage output (0 to 10 V)
*
1
0 V 0.10 V 0.12 V 10 V
*1 The analog output current from the connected equipment should be 20 μA or less when selecting 0 to 10 V.
When 20 μA or more current flows, it is possible that the accuracy is not satisfied at less than or equal to 0.5 V.
* D or H fluctuates depending on the setting of the zero cut-off function.
When the zero cut-off function is set to “0,” the flow rate display value starts from 0 L/min., but in conditions other than
horizontal installation and supply pressure of 0.35 MPa, the output may not be 0 L/min.
13
PF2M7(-L) Series

Other manuals for SMC Networks PF2M7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks PF2M7 Series and is the answer not in the manual?

SMC Networks PF2M7 Series Specifications

General IconGeneral
BrandSMC Networks
ModelPF2M7 Series
CategorySwitch
LanguageEnglish

Related product manuals