• 27 •
Disconnect HP coupling. Start A/C system with LP coupling
connected, press ENTER.
The A/C system will recover the refrigerant into the service hoses,
then the following screen will be displayed:
Disconnect LP coupling, then press ENTER to continue:
The machine will recover the residual refrigerant into the service
hoses, then the following screen will be displayed:
Procedure is now successfully completed.
Press PRINTER to print the receipt of the procedure. Press ENTER
to exit...
SERVICES
The machine keeps track of the operations done on refrigerant
fluid: recovery, system refilling, inner bottle filling. For any
operation, a record is made with date, time, type of operation,
quantities involved, plate number, inner bottle refrigerant fluid
availability. From the MAIN MENU:
Select the MANUAL PROCEDURE, the following screen will be
displayed:
R134a
mm/dd/yyyy
hh:mm
xxxxxxx
AUTOMATIC MANUAL SERVICES
SETUP
MAINTENANCE INFO
R134a MANUAL PROCEDURE
xx psi
EMPTY HOSES
Empty hoses
Hoses pressure
R134a MANUAL PROCEDURE
CHARGE
Disconnect LP coupling, from A/C system and
Press ENTER
R134a MANUAL PROCEDURE
EMPTY HOSES
End Of Procedure
gas charged xxx lb
Press ENTER to continue
2015
SEARCH BY
PLATE
SEARCH BY
DATE
EXTRACT
ARCHIVE
YEAR SELECTION:
R134a SERVICE ARCHIVE
2017
● 2016
2015
EMPTY HOSES