Option 7
2 IN/2 OUT option
Main available/Gen available output
contacts.
The contact closes as soon as the
source is available.
A 3 minutes power off
action is required before
startup to allow option
recognition.
Identification Terminals Type Feature Rating
a 9-10 Output Main available information
b 11-12 Output Gen available information
230 Vac - 5 A - 1150 VA
Max operations ≤ 10
5
- Galvanic insulation
2,5 kV (1 min 50 Hz)
ATI 057 A GB