ATySp - Annexe II
119
EN

5
TIMERS VALUE
  M-G M-M
2ST 0030 SEC

This time delay is started as soon as the genset start




ODT 0003 SEC





Note: This time delay setting value in the Zero position is
applicable with SI and/or SII available.
When a transfer is initiated after a loss of source, the time
delay starts counting down from the loss of source.

TOT UNL



Note 1: If the value is set at UNL, the TOT is stopped
either when the input is opened, or via the validation key.
Note 2: When set to UNL, the test on load duration timer
is deactivated as the duration becomes unlimited.
ATTN: Set to UNL when using the engine exerciser


TOT 0000 SEC



Note: TOT is visible in the timers menu when TOT
(LIM/UNL) above is set to LIM.

T3T 0000 SEC




TFT UNL



Note 1: If the value is set at UNL, the TFT is stopped
either when the input is opened, or via the validation key.
Note 2: When set to UNL, the test on load duration timer
is deactivated as the duration becomes unlimited.
ATTN: Set to UNL when using the engine exerciser


TFT 0600 SEC




Note: TFT is visible in the timers menu when TOT
(LIM/UNL) above is set to LIM.

E1T 0005 SEC





Note: E1T is visible in the timers menu when at least
1 input is configured as EON.
