TIMERS VALUE
M-G M-M
E2T UNL
set to UNL, the test on load duration timer is deactivated
Note 1: If the value is set at UNL, the TOT is stopped
either when the input is opened, or via the validation key.
Note 2: E2T is visible in the timers menu when at least
1 input is configured as EON.
E2T 0010 SEC
Note: E2T duration timer is visible in the timers menu
when at least 1 input is configured as EON and with
E2T (UNL/LIM) set to LIM.
E3T 0005 SEC
Note: E3T duration timer is visible in the timers menu
when at least 1 input is configured as EON and with
E2T (UNL/LIM) set to UNL.
E5T 0005 SEC
Note: E5T is visible in the timers menu when at least
1 input is configured as EON.
E6T LIM
set to UNL, the test off load duration timer is deactivated
Note 1: If the value is set at UNL, E5T is stopped either
when the input is opened, or via the validation key.
Note 2: E6T is visible in the timers menu when at least
1 input is configured as EOF.
E6T 0600 SEC
Note: E6T is visible in the timers menu when at least
1 input is configured as EOF.
E7T 0005 SEC
Note: E7T is visible in the timers menu when at least
1 input is configured as EOF.
LST 0004 SEC
time delay corresponds to the time available to perform
any load shedding operations downstream before the
ATy
EET 0168 H
EDT 0000 SEC
Note: