20
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
11. TECHNICAL SPECIFICATION
Models
1 1 (LB) 2 2 (LB) 3 3 (LB)
Nominal Power
VA/W 1000/800 2000/1600 3000/2400
Input/Output phases 1/1 1/1 1/1
Electrical Specifications - Input
Mains voltage (Vin) Vin 110 to 300 V Derating to 50 % @ 110 V input
Input frequency Hz 45 to 55/54 - 66
Input power factor ≥ 0.99
THDI < 5 % with full load
Electrical Specifications - Output
Output Voltage V 208/220/230/240 V ± 2 %
Output power must derating to 90 % when the output voltage rate be set with 208 V
Frequency Hz 45-55/54 to 66 Hz (50/60 Hz ± 0.2 Hz in Battery Mode or Converter Mode)
Overload – Normal
Mode (@ 25°C)
1 m
30 s
10 s
1 s
%
105 to 110
110 to 125
125 to 150
> 150
Crest Factor 3:1
Voltage distortion % < 5 % Non Linear Load; < 3 % Linear Load
Electrical Specificationsn - Battery
Type
Sealed lead acid maintenance free-expected life 3/5 years
Voltage
36 96 96
BUT
> 5 min - > 9 min - > 5 min -
Charger
-8 A-8 A-8 A
Enviroment
Operating temperature °C 0 to 40
1
Relative humidity % 20 to 90 No Condensing
Max. altitude m < 1000 m without derating
Acoustic noise dBA up to 50 dB at front 1 m
Standards
Safety EN 62040-1, EN 60950-1
EMC EN 62040-2
Product Certification CE
Protection Level IP20
Mechanical Characteristics with standard batteries
Dimensions (W x D x H) mm 145 x 400 x 220 192 x 460 x 347 192 x 460 x 347
Weight kg 13 7 31 13 31 13
1. 15-25 °C for a longer battery life.