37
ENGLISH
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
21. TECHNICAL SPECIFICATION
Models
6 6 (LB) 10 10 (LB)
Nominal Power
VA/W
6000/5400 10000/9000
Input/Output phases 1/1 1/1
Electrical Specifications - Input
Mains voltage (Vin) Vin 220/230/240 V; 1 Ph (L/N) + PE, 3-wire
Input frequency Hz 50/60
Input power factor 0.99
THDI < 5 % with full load
Electrical Specifications - Output
Output Voltage V 208/220/230/240 V ±1 %; 1 Ph (L/N) + PE, 3-Wire
Output power must derating to 90 % when the output voltage rate be set with 208 V,
and 80 % for 200 V
Frequency Hz 50/60 ± 0.05 %
Overload –
Normal Mode
(@ 25°C)
10 m
1 m
10 s
100 ms
kW
105 to 125
125 to 150
> 150
> 170
Overload –
Battery Mode
(@25°C)
2 m
30 s
100 ms
kW
105 to 125
125 to 150
> 150
Crest Factor 3:1
Voltage distortion < 5 % Non Linear Load; < 2 % Linear Load
Electrical Specificationsn - Battery
Type
Sealed lead acid maintenance free-expected life 3/5 years
Voltage
240 V
BUT
> 5 min - > 4 min -
Charger
-4 A-4 A
Enviroment
Operating temperature °C 0 to 40 °C
1
Relative humidity % 0 to 95 % No Condensing
Max. altitude m < 1000 m without derating
Acoustic noise dBA 50 dB at front 1 m 55 dB at front 1 m
Standards
Safety EN 62040-1, EN 60950-1
EMC EN 62040-2 C3
Product Certification CE
Protection Level IP20
Mechanical Characteristics with standard batteries
Dimensions (W x D x H) mm 428 x 970 x 720
Weight kg 73 25,5 84 29,5
1. 15-25 °C for a longer battery life.