30
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
17.4. MENU TREE
FIRST LEVEL SECOND LEVEL THIRD LEVEL
UPS STATUS
EVENT LOG
MEASUREMENTS
COMMANDS BUZZER MUTE Buzzer Mute: no
SINGLE UPS BATTERY TEST Status: battery test
Schedule battery test: no
CLEAR EPO STATUS Status EPO active
Clear: no
RESET FAULT STATE Status: Fault active
Reset fault: no
CLEAR EVENT LOG Total events: 50
Clear event log: no
RESTORE FACTORY SETTINGS Reset: no
IDENTIFICATION
SERVICE USER PASSWORD enabled/disabled
AUDIO ALARM enabled/disabled
RATED OUTPUT VOLTAGE 208/220/230/240 V
OUTPUT FREQUENCY autosensing 50/60 Hz
POWER STRATEGY normal/high ef ciency/ converter
DC START enabled/disabled
SITE WIRING ALARM enabled/disabled
AMBIENT TEMPERATURE WARNING enabled/disabled
AUTOMATIC BATTERY TESTS PERIOD 0 to 31days
AUTO RESTART enabled/disabled
AUTOMATIC OVERLOAD RESTART enabled/disabled
AUTO BYPASS enabled/disabled
SHORT CIRCUIT CLEARANCE enabled/disabled
BYPASS VOLTAGE LOW LIMIT 110 to 215 V
BYPASS VOLTAGE HIGH LIMIT 245 to 276 V
BYPASS FREQUENCY LOW LIMIT 1 to 10 %
BYPASS FREQUENCY HIGH LIMIT 1 to 10 %
HE VOLTAGE LOW LIMIT 1 to 10 %
HE VOLTAGE HIGH LIMIT 1 to 10 %
HE FREQUENCY LOW LIMIT 1 to 10 %
HE FREQUENCY HIGH LIMIT 1 to 10 %
BATTERY QUANTITY 19/20/21
SET RUNNING TIME Day:hour:minute:second
0000:0000:00~9999:23:59:59
LCD CONTRAST -5 to +5