- 44 -
1. Autotest Fast
OK
Start Autotest
Press “Ok” to start
Testing 59.S1...
Wait
Test 59.S1 OK!
Wait
Testing 59.S2...
Wait
Test 59.S2 OK!
Wait
Testing 27.S1...
Wait
Test 27.S1 OK!
Wait
Testing 27.S2...
Wait
Test 27.S2 OK!
Wait
Testing 81>S1...
Wait
Test 81>S1 OK!
Wait
Testing 81>S2…
Wait
Test 81>S2 OK!
Wait
Testing 81<S1...
Wait
Test 81<S1 OK!
Wait
Testing 81<S2...
Wait
Test 81<S2 OK!
Press “Ok”
Auto Test OK!
Press “Down”
59.S1 threshold 253V 900ms
Press “Down”
59.S1: 228V 902ms
Press “Down”
59.S2 threshold 264.5V
200ms
Press “Down”
59.S2: 229V 204ms
Press “Down”
27.S1 threshold 195.5V
1500ms