HYD 5-20KTL-3PH User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd。
Permanent failure of
unbalanced output
current
Input mode setting error
permanent failure
Check the PV input mode
(parallel/independent mode) Settings for the
inverter. If not, change the PV input mode.
Input overcurrent
permanent fault
Input hardware
overcurrent permanent
failure
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
Bus voltage unbalanced
permanent failure
Check the USB port of the inverter
Check the Wifi port of the inverter
Check the bluetooth connection of the
inverter
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
Communication board
EEPROM error
Communication board
FLASH error
SCI communication
error (DC)
SCI communication
error (AC)
SCI communication
error (Fuse)
Contact for technical support and software