© Softing Industrial Automation GmbH 41
Chapter 8 - Technical Data
8 Technical Data
18 VDC ... 32 VDC; SELV/PELV supply mandatory
Typical input current is 200 mA; maximum is 1 A (considering the rush-
in current at switch-on).
2x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
Operating temperature, horizontal
DIN rail installation
-40 °C ... +50 °C (0 mm minimum distance)
-40 °C ... +55 °C (22.5 mm minimum distance)
Operating temperature, vertical DIN
rail installation
-40 °C ... +35 °C (0 mm minimum distance)
-40 °C ... +40 °C (22.5 mm minimum distance)
10 % ... 95 % (non-condensing)
Indoor use only; no direct sunlight
100 mm x 22.5 mm x 105 mm
IT network / cloud connection
OPC UA (Server, 20,000 items in total), MQTT (Publisher, up to 1,000
topics)
Industrial network connectivity
OPC UA, controllers (Siemens SIMATIC S7-300/400/1200/1500, Modbus
TCP-compatible controllers, Siemens SINUMERIK 840D Solution Line)
Supported development tools
SIMATIC Step 7, TIA Portal, Siemens NCVar Selector