EasyManua.ls Logo

Software House RM2-4000-PI26 - Reader Setup and Configuration

Software House RM2-4000-PI26
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting up the reader
9
Wiring the Inputs,
Outputs, Reader Bus
Figure 5 shows RM-4 P1 and P5 wiring.
FIGURE 5. RM-4 Wiring Requirements
NOTES SW3-7 and SW3-8 refer to the Beeper on the RM-4.
P3 BEEP refers to the Beeper on the read head, if it exists. There is no Beeper on the
reader read heads. Some third-party readers that are connected to a standalone reader
have beepers.
SETTING UP THE
READER
To Set Up the Reader:
1. Set the Reader Address Switch, SW1 (a 16 position rotary switch, see Figure 5), to a
number from one to eight. Each Reader along the bus must have a unique address.
2. The SW3-1, SW3-2, SW3-3, and SW3-6 Configuration Switches are factory preset
for the readers, as shown in Figure 5 on page 9.
3. Note that you can override SW3-4, SW3-5, SW3-7 and SW3-8 if desired.
To properly terminate an RS-485 line, only the last unit on the bus should have
SW3-5 in the On (closed) position.
DRAFT

Related product manuals