Chapter 3: Power Optimizer Installation
SolarEdge Power Optimizers Installation Guide – MAN-01-00112-1.2
13
For mounting on rails with sliding nut fasteners, or on an un-grounded structure
(such as a wooden
structure): Connect an equipment-grounding conductor to the grounding terminal according to the
supplied instructions (the terminal should be purchased separately
1*
). The grounding terminal
accepts a wire size of 6-14 AWG, and must be sized for equipment grounding per NEC 250.122
requirements. Tighten the screws connecting the power optimizer to the frame and the grounding
terminal screw. Apply torque of 9.5 N*m / 7 lb*ft.
WARNING:
The metallic enclosure o
f the power optimizer must be grounded in accordance with the
requirements of the Local and National Codes
.
L'enceinte métallique de l
optimiseur de puissance doit être mise à la
terre en accord avec les
régulations locales et nationales..
Figure 5: Power optimizer grounding terminal
For rest of the world – all power optimizers are double insulated and grounding is not required.
:
Step 4, Providing
6 Verify that each power optimizer is securely attached.
*
For additional information, refer to http://www.solaredge.com/files/pdfs/se-product-update-dcd-c-grounding-lug.pdf.
Optional grounding
terminal