EasyManuals Logo

SolarEdge SE5000 User Manual

SolarEdge SE5000
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
SE4K SE5K SE7K SE8K SE9K SE10K SE12.5K Unit
Protective class Class I
Utility monitoring,
islanding protection,
configurable Power
Factor, country
configurable
thresholds
Yes
Overvoltage category III
Input
Maximum DC power
(Module STC)
5400 6750 9450 10800 12150 13500 16850 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
900 Vdc
Nominal DC input
voltage
750 Vdc
Maximum input
current
7 8.5 12 13.5 15 16.5 21 Adc
Maximum back-feed
current
0 Adc
Reverse-polarity
protection
Yes
Ground-fault
isolation detection
700kΩ Sensitivity
Overvoltage category II
Maximum inverter
efficiency
98 %
European weighted
efficiency
97.3 97.3 97.3 97.5 97.5 97.6 97.7 %
Night-time power
consumption
< 2.5 W
-Three Phase System Installation Guide MAN-01-00057-4.1
106Technical Specifications - Three Phase Inverters (Europe &APAC)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge SE5000 and is the answer not in the manual?

SolarEdge SE5000 Specifications

General IconGeneral
ModelSE5000
ManufacturerSolarEdge
CategoryInverter
AC Output Power5000 W
Efficiency98.3%
CoolingNatural convection
Protection RatingIP65
Rated AC Power5000 W
Max. AC Power5000 VA
Maximum Input Voltage480 V
Number of MPP Trackers1
Max. Input DC Voltage480 V
Operating Temperature Range-25°C to 60°C
AC Voltage230 V

Related product manuals