Setting
Setting
>
0 0 0 0
User Password
> Mode Select
Disable
Load Management
92
93
10) User Password
The default password for the end user is "0000", where you can reset the
new password and press the up/down key to increase or decrease the
value. Press "Enter" to confirm the value and jump to the next digit. When
all passwords have been entered and confirmed, press "OK" to set the
password successfully.
9) Dry Contact
When the user uses the inverter communication control external device
function, you can enter here to set the parameters of the external
response control. For the setting method, please refer to the user manual
of the compatible external device.
If the user uses the inverter dry contacts to control external devices (such
as heat pumps) through the Adapter box, please refer to the Adapter box
quick installation manual to set the parameters here.
8) Peak Shaving mode
.
Set "PeakLimits1/2" to limit the power that loads get from the grid. Once the
power of loads exceeds "peak limits" during the peak hours, the PV and
battery will discharge energy for loads and thus reduce the amount of energy
purchased from the grid. In non-peak hours, discharging of the battery is not
allowed. If you want to get electricity from the grid, set "ChargeFromGrid" to
"Enable". "Disable" is the default setting. When you select "Enable" and the
actual battery SOC is less than "MAX_SOC "(settable), the battery can be
charged from the grid at no more than "ChargePowerLimits" (settable)
power.
Range of "ChargePowerLimits": 0 W~rated power (W)
The range of "MAX_SOC" is 10%–100%; the default value is 50%.
Range of "Reserved_SOC" is10%–100%; the default value is 50%.
“Reserved_SOC" is the battery capacity saved for the next peak shaving in the
non-peak shaving period.
ShavingStartTime
07:00
DisChgPeriod1
ChargeFromGrid
Disable
Reserved_SOC
50%
ReservedSOC
>
Peak shaving mode
User Setting
>DisChgPeriod1
DisChgPeriod2
ChargeFromGrid
Peak shaving mode
DisChgPeriod1
DisChgPeriod1
ShavingEndTime
15:00
ShavingLimits1
0W
DisChgPeriod1
>DisChgPeriod2
ChargeFromGrid
Peak shaving mode
DisChgPeriod2
DisChgPeriod2
DisChgPeriod2
ShavingStartTime
19:00
ShavingEndTime
23:00
ShavingLimits2
0W
DisChgPeriod1
DisChgPeriod2
>ChargeFromGrid
Peak shaving mode
ChargeFromGrid
ChargeFromGrid
ChargeFromGrid
ChargePowerLimits
1000W
MAX_SOC
50%
DisChgPeriod2
ChargeFromGrid
>Reserved_SOC
Peak shaving mode
This setting is for enabling peak shaving mode.
"DisChgPeriod1" and "DisChgPeriod2" are two discharging periods you can
set. Set "ShavingStartTime1" (default value: 7:00) and "ShavingEndTime1
(default value: 15:00) under "DisChgPeriod1" , and "ShavingStartTime2
(default value: 19:00) and "ShavingEndTime2" (default value: 23:00) under
"DisChgPeriod2" to define the peak hours of electricity.