Setting failed!
Advance Password
Set OK!
Advance Password
29) Advance Password
Here you can reset the advanced password. "Set OK!" is displayed on
success, and “Setting Failed! will also be displayed on failure.
26) HotStandby Setting
This function is mainly to save the capacity of the battery. When PV has no
power and the inverter has no output power, the inverter will enter
“HotStandby” status. When the power of loads is higher than 100W, the
inverter will exit “HotStandby” status.
It is “ Disable by default, setting “Enable the inverter will enter “HotStandby”
status.
HotStandby Setting
Enable/Disable
Pgrid Bias
Pgrid Bias
Disable/Grid/INV
25) ExternalGen
The set value of power must meet the following two conditions when
the maximum charging power of batteries is to be set.
1) The value of Max Charge Power is less than that of rated power of the
generator minus total load power.
2) The value of Max Charge Power is less than or equals that of rated
power of the inverter.
104
105
Setting
Setting
28) Battery Charge EVC
Here you can set Enable to allow the battery to discharge energy
to EV Charger. When you set Disable ‘‘, battery discharging energy
to EV Charger is not allowed.
Disable/Enable
Battery charge EVC
HotStandby Setting
Function Control
Enable Disable
External Gen
Function Control
ATS Control
External Gen
MaxChargePower
0W
External Gen
Forced Charg Period
Start Time
00:00
External Gen
Allowed Disc Period
Start Time
00:00
External Gen
Allowed Disc Period
End Time
00:00
External Gen
Char&Disc Period2
Enable Disable
External Gen
Forced Charg Period
Start Time 2
00:00
External Gen
External Gen
Forced Charg Period
End Time
00:00
External Gen
Forced Charg Period
End Time
00:00
External Gen
Forced Charg Period
End Time
00:00
External Gen
Forced Charg Period
End Time 2
00:00
Allowed Disc Period
Start Time 2
00:00
External Gen
Allowed Disc Period
End Time 2
00:00
External Gen
Charge from Gen
Enable/Disable
External Gen
Charge battery to
10%
Charge from Gen
Function Control
Dry Contact
ExternalGen
MaxChargePower
0W
ExternalGen
Start Gen Method
reference soc/immediately
ExternalGen
External Gen
Switch on SoC
0%
ExternalGen
Charge from Gen
Enable Disable
External Gen
Charge battery to
10%
ExternalGen
Switch off SoC
0%
MaxRunTime
Min
ExternalGen
ExternalGen
MaxRestTime
Min
Char&Disc Period
Enable Disable
ExternalGen
ExternalGen
Charg Period
Start Time
00:00
Charg Period
End time
00:00
ExternalGen
External GenExternalGen
ExternalGen
End Time
00:00
Allowed Disc Period
Start Time
Allowed Disc Period
00:00
ExternalGen
Char&Disc Period2
Enable Disable
ExternalGen
27) Pgrid Bias
Here you can set whether to discharge more to the grid or prefer to
take power from the grid. If disable is selected , means no preference. If
Grid is selected, the inverter will be biased to discharge the mains; if
INV is selected, the inverter will be biased to take power from the
mains.

Other manuals for SolaX Power X1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolaX Power X1 Series and is the answer not in the manual?

SolaX Power X1 Series Specifications

General IconGeneral
Protection RatingIP65
AC Voltage Range180V-280V
THDi<3%
Warranty5 years
MPPT Voltage Range520V
Number of MPPTs1
Nominal AC Voltage230V
Power Factor0.8 leading to 0.8 lagging
European Efficiency97%
ProtectionDC Reverse-Polarity Protection, AC Short-Circuit Protection
Operating Temperature Range-25°C to +60°C
CoolingNatural
CommunicationWiFi, Ethernet, GPRS
Frequency50Hz / 60Hz