Schematic diagram of the inverter PV connected.
f ) Insert the wire into plug forcibly, when a "click is heard or felt the pin contact
assembly is seated correctly. Then tighten the cable nut.
e) Loosen the cable nut from the DC connector. Then insert the wire with pin
contact through the cable nut.
plug
cable nut
Installation Installation
Grid Connection
Ø
X3-MIC G2 series inverters are designed for three phase grid. Rated grid voltage
is 230 V, frequency is 50/60 Hz. Other technical requests should comply with
the requirement of the local public grid.
Micro-breaker should be installed between inverter and grid, any loads
should not be connected with inverter directly.
Table 4 Cable and Micro-breaker recommended
Incorrect Connection between Load and Inverter
L1,L2,L3,N Cable
4-5 mm
PE Cable
4-5 mm 4-5 mm 5-6 mm
Model
*The parameters have some differences because of different environment and material. Please
choose appropriate cable and micro-breaker according to the local conditions.
5-6 mm
Micro-breaker
16 A 16 A 16 A 20 A 32 A 32 A
32 A
32 A
5-6 mm 5-6 mm 5-6 mm
2.5-5 mm 2.5-5 mm 2.5-5 mm
2.5-6 mm
2.5-6 mm 2.5-6 mm 2.5-6 mm 2.5-6 mm
X3-MIC-3K-G2 X3-MIC-4K-G2 X3-MIC-6K-G2 X3-MIC-8K-G2 X3-MIC-12K-G2X3-MIC-10K-G2 X3-MIC-15K-G2X3-MIC-5K-G2