6 Terminals Review
________________________________________________________________________________________________
4. TERMINALS REVIEW
General Notes:
Use 75°C copper wires only
Control Supply
110-240V 50/60Hz or DC (+10% / -15%)
Phase/Positive Lead .................................... 
Neutral/Negative Lead ................................. 
Ground ......................................................... 
The TPR-6 incorporates four relays, each with 1-C/O contact, rated 8A/250 VAC, 2000VA resistive.
See I/O SETTINGS (page 2).
Note:
Tighten terminals 18, 19, 20 to 7 in-lbs
Output Relay A - Alarm
Relay contacts can be configured as one of:
ALARM RELAY contact changes upon fault and returns after reset (after fault has been removed).
ALARM FAIL-SAFE logic contact changes when control voltage is connected and returns upon fault.
Relay is energized when control voltage is connected. Upon fault, which is designated as Alarm, the
relay de-energizes. This relay can be used to sense control supply outage.
TRIPPING / ALARM - Relay can be assigned to specific faults that are enabled as alarm or trip.
Common ........................ .............................. 1
N.C ............................................................. 2
N.O .........................................…................. 3
Output Relay B - Trip
Relay contacts can be configured as one of:
TRIP Relay contact changes upon fault and returns after reset (after fault has been removed).
TRIP FAIL-SAFE logic contact changes when control voltage is connected and returns upon fault.
TRIPPING / ALARM - Relay can be assigned to specific faults that are enabled as alarm or trip.
Common ……………………………………... 4
N.C ............................................................. 5
N.O .............................................................. 6
Output Relay C - Programmable
Relay can be assigned to specific faults that are enabled as alarm or trip.
Common ………………………………........ 7
N.C .............................................................. 8
N.O .............................................................. 9
Output Relay D - Programmable
Relay can be assigned to specific faults that are enabled as alarm or trip.
Common …………………………………….. 10
N.C .............................................................. 11
N.O .............................................................. 12
Discrete Logic Inputs
Programmable inputs from N.O or N.C. contacts (See I/O Settings)
Input voltages are 110-240V 50/60Hz or DC (+10% / -15%)
Input 1 ......................................................... 13
Input 2 ......................................................... 14
Common ...................................................... 15