CAUTION:
Risk of electric shock from energy stored in capacitors of the Inverter.
Do not remove cover for 5 minutes after disconnecting all power sources
(service technician only). Warranty may be voided if the cover is removed
without unauthorized.
CAUTION:
The surface temperature of the inverter can exceed 75 (167F).
To avoid risk of burns, DO NOT touch the surface when inverter is operating.
The inverter must be installed out of reach of children.
CAUTION:
The PV array (Solar panels) supplies a DC voltage when they are exposed to
sunlight.
WARNING:
To reduce the risk of fire, over-current protective devices (OCPD) are
required for circuits connected to the Inverter. The DC OCPD shall be installed
per local requirements. All photovoltaic source and output circuit conductors
shall have disconnects that comply with the NEC Article 690, Part II.
All Solis S6 Single Phase Inverters feature an integrated DC switch.
CAUTION:
Risk of electric shock. Do not remove cover. There is no user serviceable
parts inside. Refer servicing to qualified and accredited service technicians.
WARNING:
Do not touch any inner live parts until 5 minutes after disconnection from
the utility grid and the PV input.
2. Safety Instructions 2. Safety Instructions
2.3 Notice For Use
The inverter has been constructed according to the applicable safety and technical
guidelines. Use the inverter in installations that meet the following specifications only:
Permanent installation is required.
2.4 Notice for Disposal
This product shall not be disposed of with household waste. They should
be segregated and brought to an appropriate collection point to enable
recycling and avoid potential impacts on the environment and human health.
Local rules in waste management shall be respected .
.6. .7.
WARNING:
No live construction is allowed, and before installation, ensure that the
equipment is in good condition.
WARNING:
Destruction of the inverter due to overvoltage;Damage to the product due to
ground fault on DC side during operation Damage to the product due to sand,
dust and moisture ingress if the DC inputs are not closed.
This document does not replace any regional, state, provincial, federal or national laws,
regulations or standards that apply to the installation, electrical safety and use of the
product. Solis assumes no responsibility for the compliance or non-compliance with
such laws or codes in connection with the installation of the product.
Use Solis products only in accordance with the information provided in the enclosed
documentation and with the locally applicable laws, regulations, standards and
directives. Any other application may cause personal injury or property damage.
The product must only be used in countries for which it is approved or released by
Solis and the grid operator.
All components must remain within their permitted operating ranges and their
installation requirements at all times.
The electrical installation must meet all the applicable regulations and standards.
The inverter must be installed according to the instructions stated in this manual.
The inverter must be installed according to the correct technical specifications.
To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before
the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply
Main Switch (AC) must be switched off before the solar panel's DC isolator shall be
switched off.

Other manuals for SOLIS S6 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SOLIS S6 Series and is the answer not in the manual?

SOLIS S6 Series Specifications

General IconGeneral
Number of MPPTs2
THDi<3%
DC SwitchYes
Max. AC Output Power6000W
Rated AC Output Power6000W
Max. AC Apparent Power6000VA
Rated Grid Voltage230V
Grid Voltage Range180V-280V
Rated Grid Frequency50Hz/60Hz
Grid Frequency Range45-55Hz / 55-65Hz
ProtectionDC Reverse-Polarity Protection, AC Short-Circuit Protection
Operating Temperature Range-25°C to 60°C
CoolingNatural Cooling
CommunicationWiFi/GPRS