4.1.2.3 DC Voltage Input
Connection Procedure
• Disconnect power from the system.
• Remove the grey protective cover from the appropriate input module
• Configure the jumper switches as shown below (i.e. J9 and J14 switched ON, all others
OFF)
• Remove R16 and R18 (located above J13) from the input module.
• Fit conventional ¼watt resistors to positions SR1 and SR2 using values from the following
table.
For alternative voltage inputs contact Status Scientific for appropriate resistor values.
• Connect the detector head to PL1 observing the above diagram.
• Connect power to the system.
• Refit grey protective cover.
• Perform software configuration (refer to ‘MCU Software Configuration and System
Calibration Manual’).
• Perform system calibration. Refer to ‘MCU Software Configuration and System Calibration
Manual’ and detector head manufacturers instructions.
The Input Modules can be configured to accept signal levels in voltage form.
SR1 and SR2 are used to scale the voltage to the appropriate level.