TD06/001
Issue:
6
Change Note:
1696
Page 4-10
4.1.2.4 Pellistor Only Gas detectors
Connection Procedure
Note: For use in hazardous areas, the pellistors must be housed in an Exd enclosure mounted on
an Exe terminal housing.
DO NOT connect the pellistors at this time.
Remove the grey protective cover from the appropriate input module.
Configure the jumper switches as shown below (i.e. J8 & J9 switched ON, all others OFF)
Connect a voltmeter between pins 22 (+V) and 24 (0V).
Adjust VR1 and VR2 until the correct voltage can be measured for the pellistors being
used (SSCL pellistors require 2.0V 0.01V).
VR1 & VR2 provide coarse and fine output voltage adjustment respectively.
Note: Connecting a voltage of greater than 2.2V will cause irreparable damage to the
pellistors.
Connect the pellistors to the input module observing the above diagram.
Check that the voltage across the pellistors remains at 2.0V 0.01V, adjust if necessary.
Note: Measure the voltage at the pellistors, not at the input module terminals.
Refit the grey protective cover.
Perform software configuration (refer to ‘MCU Software Configuration and System
Calibration Manual’).
Perform system calibration.
J12
J11
J10
J9
J8
J7
J6
J14
J13
This configuration allows the direct connection of
pellistors (no electronics) to the input module.
PL1
Terminals
0V
21
22
23
24
Signal
Sensing
Circuit
Variable
Voltage
Output
0V
Bk
B
R
G
Detector
Signal
Compensator
Earth
Exd Flammable
Gas Sensor
Exe
Enclosure
Exe
Gland
Lock
Nut
Earth Continuity
Plate
If EARTH continuity is not
maintained via gland (e.g.
plastic gland) then connect
cable screen or armour to
EARTH terminal as shown.
Control Unit Gland Plate
Link to cable screen or Armour
Screened/Armoured Cable
Gland Plate Earth Stud
Detector
Signal
Compensator